400 V microgrid current: checking the path from VGRID PCS to switchboard
Summary: Use three-phase kVA for a first current estimate, then check documented ratings, charging modes, cables and protection rather than selecting from kW alone.
400 V microgrid design notes · 2/10
Work through distribution currents circuit by circuit. The PCS branch charges and discharges, and the utility meter does not describe every internal bus section. A balanced 400 V example makes the distinction clear.
Concept illustration for this topic, not an actual project, equipment wiring diagram or approved system configuration.
Relate kW, kVA and current
For a balanced three-phase teaching case at 400 V line-to-line, I≈S×1000/(√3×400). An assumed 100 kVA gives about 144.3 A. If the input is 100 kW instead, power factor is also needed; the same current cannot simply be reused.
Keep calculation and documented ratings separate
H135K V1.0 physical page 7 lists 135 kVA and 196 A; B750K V1.4 physical page 6 lists 750 kVA and 1086 A. A general formula explains scale, not permission to overwrite nameplate data. Confirm the supplied revision, terminals and site derating.
Check charging and discharging for each circuit
Calculate the PCS branch, common bus, transformer entrance and load feeders separately for each mode. Charging is demand and discharging is supply. Multiple sources can make a local section carry more current than the utility entrance records. One total does not describe every conductor.
Review cables, switches and faults together
Rated current is only the start. Installation method, temperature, voltage drop, parallel conductors, fault withstand and selectivity belong in the design. An islanded PCS current limit is not the short-circuit capability of a strong utility source; validate protection for every supply mode.
Document the calculation boundary
Record voltage, mode, continuous current, short events, cable conditions and protection basis for each circuit. This example specifies neither a fixed cable size nor a breaker rating. Select and accept them using approved drawings and equipment data.
Related VGRID product documentation
Submit a project assessment for engineering review of actual conditions
Continue this series
- Building a 400 V microgrid: the roles of H135K, M200K and B750K
- Battery energy for a 400 V microgrid: backup time with H135K and B750K
References
Model descriptions follow the cited revisions; examples use the stated assumptions. Final configuration and test conditions need project confirmation. Site functions have not been independently verified here.
FAQ
How do you calculate three-phase current at 400 V, and how many amps is 100 kVA?
For a balanced three-phase teaching case at 400 V line-to-line, I≈S×1000/(√3×400). An assumed 100 kVA gives about 144.3 A. If the input is 100 kW instead, power factor is also needed; the same current cannot simply be reused.
What if calculated current differs from the PCS datasheet?
H135K V1.0 physical page 7 lists 135 kVA and 196 A; B750K V1.4 physical page 6 lists 750 kVA and 1086 A. A general formula explains scale, not permission to overwrite nameplate data. Confirm the supplied revision, terminals and site derating.
Does rated current alone determine cable size?
Rated current is only the start. Installation method, temperature, voltage drop, parallel conductors, fault withstand and selectivity belong in the design. An islanded PCS current limit is not the short-circuit capability of a strong utility source; validate protection for every supply mode.