kW, kVA, kvar and power factor: three power quantities

kW, kVA, kvar and power factor: three power quantities

Summary: Read active, apparent and reactive power, with a 100 kVA example showing why power factor matters.

Concept illustration for this topic, not an actual project, equipment wiring diagram or approved system configuration.

Electrical units · 5/10

Generators and transformers often list kVA while loads list kW. Look at power factor before treating different numbers as an error.

Three quantities and their units

Active power P uses W or kW, apparent power S uses VA or kVA and reactive power Q uses var or kvar. Equipment may have both active- and apparent-power limits; passing one does not settle selection.

Using power factor

Total PF=P/S. Assuming S=100 kVA and PF=0.8 gives P=80 kW. These are conditions of the example, not a universal 0.8 factor for every load.

Reactive power is not another quantity of active energy

Under applicable sinusoidal steady-state conditions, S²=P²+Q²; the example gives 60 kvar. With harmonics, use the relevant measured quantities and model rather than only this simple power triangle.

Compare the actual operating case

Record load kW, kVA, PF and imbalance together. Compare them with the relevant PCS capability. Whether reactive operation reduces available capacity requires model-specific evidence, not an unconditional reading of an adjustable range.

Related reading

Export limitation on a 400 V microgrid: metering and VGRID PCS control

References

The examples explain units; they are not equipment specifications or a project design.

FAQ

How many kW is 100 kVA at a power factor of 0.8?

Total PF=P/S. Assuming S=100 kVA and PF=0.8 gives P=80 kW. These are conditions of the example, not a universal 0.8 factor for every load.

Why must PCS kVA be checked even when its kW rating is sufficient?

Active power P uses W or kW, apparent power S uses VA or kVA and reactive power Q uses var or kvar. Equipment may have both active- and apparent-power limits; passing one does not settle selection.

Why does the same kW require more kVA at a lower power factor?

From PF=P/S, S=P/PF. At the same active power, a lower power factor requires more apparent power. Check both the equipment's kW and kVA limits.