# Battery energy for a 400 V microgrid: backup time with H135K and B750K

Define the backup task first, then separate AC energy, usable SOC and battery power limits. Enough kWh does not by itself establish sufficient PCS output.

400 V microgrid design notes · 3/10

Begin battery sizing with the circuits that must remain on. Controls, a complete production line and an intermittent pump need different energy even when the requested backup time is the same.

Concept illustration for this topic, not an actual project, equipment wiring diagram or approved system configuration.

Define what stays on

List essential, deferrable and shed-able circuits and acceptable interruption. Different load scopes for H135K or B750K produce different starting calculations. Installed plant power must not be substituted for actual average backup demand.

Calculate AC energy explicitly

Teaching assumptions: 60 kW average essential load for two hours requires 120 kWh AC. If that project also assumes an 80% usable SOC window and 90% relevant supply-path efficiency, initial nominal energy is about 120/(0.8×0.9)=166.7 kWh. These are not product guarantees and omit further ageing and site allowances.

Check whether the battery can deliver the power

Review allowed current, minimum voltage, temperature, SOC and dynamic BMS limits. Adequate energy may still come with inadequate continuous or starting power. AC PCS requirements and DC-side capability must be satisfied together.

Do not copy one battery design across models

Confirm model-specific voltage range, terminals, protection and supplied structure. B750K’s total current limit does not establish a fixed per-cluster current or cluster count. Similar power figures do not prove H135K and another SP family share a battery design.

Include generator handover and recharge

State when load is reduced, when a generator is requested, how energy is restored and what remains for a second outage. Thresholds and allowances need project and battery confirmation; this article supplies no universal SOC percentage.

Related VGRID product documentation

[LEONA-H135K](/en/product/leona-h135k)

[LEONA-B750K](/en/product/sp750h54pstd-2)

[Submit a project assessment for engineering review of actual conditions](/en/blog/category/guides#assessment-form)

Continue this series

[400 V microgrid current: checking the path from VGRID PCS to switchboard](/en/blog/400v-pcs-current-switchboard-checks)

[Operating a 400 V solar–storage–diesel microgrid with VGRID PCS](/en/blog/400v-solar-storage-diesel-dispatch)

References

Model descriptions follow the cited revisions; examples use the stated assumptions. Final configuration and test conditions need project confirmation. Site functions have not been independently verified here.

[LEONA-H135K · V1.0 · 2026-10-15 · PDF p.7](/uploads/2026/11/verified-specs/LEONA-H135K-spec-V1.0-20261015.pdf)

[LEONA-B750K · V1.4 · 2026-10-14 · PDF pp.6–7](/uploads/2026/11/verified-specs/LEONA-B750K-spec-V1.4-20261014.pdf)

[Schneider Electric — Calculation rules when integrating solar and storage](https://www.electrical-installation.org/enwiki/Calculation_rules_when_integrating_solar_and_storage)

## Which loads should be included when sizing a microgrid battery for two hours of backup?

List essential, deferrable and shed-able circuits and acceptable interruption. Different load scopes for H135K or B750K produce different starting calculations. Installed plant power must not be substituted for actual average backup demand.

## Why can a battery fail to power a load despite having enough kWh?

Review allowed current, minimum voltage, temperature, SOC and dynamic BMS limits. Adequate energy may still come with inadequate continuous or starting power. AC PCS requirements and DC-side capability must be satisfied together.

## Can H135K and B750K reuse one battery configuration?

Confirm model-specific voltage range, terminals, protection and supplied structure. B750K’s total current limit does not establish a fixed per-cluster current or cluster count. Similar power figures do not prove H135K and another SP family share a battery design.